tt_fan_speed_rpm
Name
Prometheus Metric Name
tt_fan_speed_rpm
Metric Path (tt-telemetry)
Schema:
{hostname}/tray{tray}/chip{chip}/tt_fan_speed_rpm
Example path:
bh-glx-c09u02/tray1/chip2/tt_fan_speed_rpm
Description
The fan speed in revolutions per minute (RPM). This value is read from ARC firmware telemetry. This metric is only created if the device reports fan RPM data.
Values
Type: Unsigned Integer
Units: Revolutions per minute (RPM)
Allowable values:
A non-negative integer representing the fan speed in RPM. For example, 3000 means the fan is spinning at 3000 revolutions per minute.
Prometheus Labels
Label Name |
Value |
|---|---|
hostname |
The host from which the metric was collected. |
hall |
The datacenter hall where the host is located. Sourced from the Factory System Descriptor (FSD). |
aisle |
The datacenter aisle where the host is located. Sourced from the Factory System Descriptor (FSD). |
rack |
The rack number where the host is located. Sourced from the Factory System Descriptor (FSD). |
shelf_u |
The shelf U position in the rack where the host is located. Sourced from the Factory System Descriptor (FSD). |
tray |
The tray (UBB) that the device is located on. |
chip |
The ASIC location within the tray. |
unit |
The unit of measurement. Always |